Can legionella grow in cold water?

On this page

Key points

  • Legionella does not multiply below 20°C, but it survives, dormant, and resumes growth the moment the water warms.
  • The cold water target is below 20°C within two minutes of running the outlet.
  • The real risk is cold water that is not cold: warm loft tanks, cold pipes strapped to hot ones, long stagnant runs.
  • A cold tap reading above 20°C is a finding, not a curiosity: trace the heat source and fix it.
  • Cold suppresses; it never kills. The control only works while the water stays cold, all the way to the outlet.

Not in water that is genuinely cold. Below 20°C, legionella survives but does not multiply; growth only begins when the water warms into the 20°C to 45°C range. That is why UK guidance sets the cold water target at below 20°C at the outlet, reached within two minutes of running.

The catch, and the thing that makes cold systems a genuine legionella risk, is that cold water in a real building is frequently not cold at all. "Cold" is a label on a pipe, not a measurement. A cold water storage tank in a loft can sit well above 20°C through the summer. A cold distribution pipe clipped to a hot one picks up heat along its whole length. By the time the water reaches the tap, the cold system may be delivering water squarely inside the growth range, with the temperature nobody checked because it was, after all, the cold tap.

Dormant is not dead

The second misunderstanding is about what cold does to the bacteria. Cold water does not kill legionella; it suspends it. Below 20°C the organism stops multiplying and lies dormant, fully viable, waiting. Warm the water again and growth resumes from exactly where it left off. This means the cold control has to be continuous. A system that is cold in winter but drifts above 20°C every summer is not controlled; it is seasonally colonised. It also means chilling is never a remediation method on its own: cooling a colonised system down stops new growth but leaves the existing population, and its biofilm, in place.

Where cold water picks up heat

Heat gain has a handful of usual suspects, and a walk of the system will find them. The cold water storage tank is the first: sited in a roof space that bakes in summer, uninsulated, sometimes with the lid missing or ill-fitting, so the stored water warms for hours every day. The cold water storage tank inspection exists precisely to catch this. Pipe routing is the second: cold pipes run through hot voids, above boilers, or touching hot pipes without insulation between them. The third is stagnation: a cold branch that is rarely drawn lets water sit in a warm building until it reaches ambient temperature, which in many buildings is above 20°C. Dead legs and little-used outlets are as much a cold-side problem as a hot-side one.

Recording your cold water temperatures

Free legionella risk assessment template

A structured Word document following the five-step approach in ACOP L8. Covers risk identification, written scheme, monitoring, and records. If it isn't written down, you can't evidence it.

Follows ACoP L8 and HSG274 Part 2. Free. No spam.

Measuring the cold side properly

Run the outlet for up to two minutes and take the temperature of the water once it has stabilised, so you are reading the supply rather than the water that was standing in the branch. Below 20°C is the target. A reading above that, or a cold tap that never runs properly cold, is a finding: note it, trace the heat source, and fix the cause, whether that is insulating the tank and its pipes, re-routing or lagging pipework, or putting the branch on a flushing regime. The legionella temperature checker walks through the technique, and legionella temperature control puts the cold target alongside the hot ones.

"Cold" is a measurement, not a label on a pipe. If your cold tap delivers 24°C, you have a warm-water system you have not been managing, and warm water is where legionella grows.

Log every cold-side reading with the date, the outlet and the result in your log book, and keep the records for at least five years. The written scheme in your risk assessment should name which cold outlets are checked and how often, so the cold side of the system is managed with the same discipline as the hot. Summer is the season to pay particular attention: the readings that pass in January are not evidence about July.

Free legionella risk assessment template

A structured Word document following the five-step approach in ACOP L8. Covers risk identification, written scheme, monitoring, and records. If it isn't written down, you can't evidence it.

Follows ACoP L8 and HSG274 Part 2. Free. No spam.

Frequently asked questions

Can legionella grow in cold water?

Not in genuinely cold water. Legionella survives in cold water without multiplying, and only starts to grow once the water warms into the 20°C to 45°C range. That is why UK guidance sets the cold water target at below 20°C within two minutes of running the outlet. The practical problem is that cold water in a real building is often not cold: a loft tank in summer or a cold pipe run next to a hot one can sit comfortably inside the growth range.

Does cold water kill legionella?

No. Cold water suppresses legionella but does not kill it. Below 20°C the bacteria stay dormant: they do not multiply, but they remain viable, and they begin growing again as soon as the water warms up. Chilling is a control that suspends growth, not a treatment that removes the organism, which is why a cold system must be kept cold continuously, not just most of the time.

Why is my cold tap running warm?

Warm cold water is heat gain somewhere in the system. Common causes are a cold water storage tank in a hot loft, cold pipes running alongside hot pipes or through warm voids without insulation, long pipe runs with little draw-off, and blended supplies downstream of a thermostatic mixing valve. It is worth investigating rather than ignoring: a cold outlet consistently above 20°C is inside the legionella growth range and should be treated as a finding, with the source of the heat traced and fixed.

What temperature should cold water be for legionella control?

Below 20°C at the outlet, reached within two minutes of running. The two minutes allow the standing water in the branch to clear so you are measuring the supply, not water that has been sitting in the pipe warming up. If a cold outlet will not get below 20°C after two minutes, investigate the storage temperature, the pipe routing and the insulation, and record the reading and the action taken.

Related water hygiene products and services from trusted UK providers will appear here.

Important This page is general guidance only. Legionella risk varies with the specific water system, its use, and the people exposed to it. You should consult a competent legionella risk assessor for advice on your premises. LegionellaCheck is an independent information service and is not affiliated with HSE, UKAS, the Legionella Control Association, or any water hygiene company. This site does not provide medical advice. If you suspect Legionnaires' disease, contact NHS 111 or your GP.